English Slovenčina українська Přihlásit Zaregistrovat se Catalog Browser Contact Us
Globální expert na kabely a kabelové systémy

About Nexans

Produkty a řešení

Služby zákazníkům

Pracovat pro Nexans

Novinky a tiskoviny

Jdi na

IEC 60502-1 Armoured (GSTA) Fire retardant

Záložka Tisknout Kontaktovat nás
IEC 60502-1 Armoured (GSTA) Fire retardant - 0.6/1 kV Power and control cables
- Armoured with galvanized steel tapes (GSTA) or aluminium tapes (ATA)
- Oil resistant
Standart
Mezinárodní  IEC 60228; IEC 60332-3-22 Cat.A; IEC 60502-1
Popis

Applications

These power and control cables are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plants...).

 

Design

Conductor:

Solid plain copper: 1.5 to 4 mm²

Stranded plain copper: 1.5 to 630 mm²

Insulation:

Cross-linked polyethylene (XLPE)

Bedding (optional):

Inner sheath acting as a filler with practically zero thickness or assembling polyester tape

Inner covering (inner sheath):

Polyvinyl chloride (PVC). Colour: black

Armour:

Galvanized steel tapes (GSTA) or aluminium tapes (ATA) for 1 core cable

Outer sheath:

Polyvinyl chloride (PVC). Colour: black. Other colour on request.

 

Core identification

1 core: black
2x to 5G cores: according to HD 308 S2
Above 5 cores: black core printed with white number
 

 

Marking

NEXANS 279 XLPE/PVC/ATA or GSTA/PVC 0.6/1 kV Nber of cores and cross section Cu IEC 60332-3-22(A) MM YYYY manufacturing number + meter marking



Related documents
  Core indentification HD308 S2  (486.9kb)
  Electrical_characteristics_IEC60502_1_GSTA  (30.3kb)



 Nahoře
Vlastnosti
Konstrukční charakteristika
Material jádra Plain copper  
Isolace PRC  
Inner sheath PVC  
Outer sheath Tight buffer  
Protection Yes  
Electrical characteristics
Rated Voltage Uo/U (Um) 0.6/1 kV  
Mechanical characteristics
Mechanical resistance to impacts Good  
Charakteristika použití
Fire retardant IEC 60332-3-22  
Oil resistance Yes  
Max. conductor temperature in service 90°C  
Operating temperature, range -20 .. 60°C  

 Nahoře
Prodejní a dodací podmínky

Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

1 core: 10 x outer diameter
Multicores: 8 x outer diameter
To be doubled during laying operations


Cables with reduced neutral on request


Související informace
IEC 60502-1 Armoured (GSTA) Fire retardant   Core indentification HD308 S2 (486 kB)
IEC 60502-1 Armoured (GSTA) Fire retardant   Electrical_characteristics_IEC60502_1_GSTA (30 kB)

Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map