Application
RHEYHALON Security cables JE-H(St)HQH with 30 minutes circuit integrity should be used for control voltages and data transfer in alarm and fire alarm systems, where a circuit integrity acc. to DIN 4102-12 of 30 minutes is required. The circuit integrity is guaranteed with a test voltages rate of 110 V.
This cable was created for installations which need a special mechanical protection (protection against rodent attack).
Design
- Conductor
Bare copper acc. to DIN VDE 40 500-4, single wire 0,8 mm ø
- Conductor taping
MICA tape
- Insulation
halogen free Polymer compound, flame retardant
- Laying up
2 cores to pairs, 4 pairs to bunches, bunches to layer
(exception 2x2x0,8 to star-quad)
- Screen
a) plastic tape
b) alu/plastic tape with drain wire, 0,8 mm ø
c) protection tape
- Armouring
zinc coated steel wire braid
- Outer sheath
thermoplastic, halogen free Polymer compound acc. to DIN VDE
207-24, compound type HM2, flame retardant
- Sheath colour
red
Standards
circuit integrity E30 DIN VDE 4102-12
insulation integrityFE180 IEC 60 331 und VDE 0472-814
halogen free IEC 60 754-2 und EN 50 267-2-1
corrosive gases IEC 60 754-2 und EN 50 267-2-2
flame retardant IEC 60 332-3 und EN 50 266-2-4 und -2-5
smoke density IEC 61 034-2 und EN 50 268-2
fire retardant IEC 60 332-1-2 und VDE 0482-265-2-1
|