About Nexans
Produkty a řešení
Služby zákazníkům
Pracovat pro Nexans
Novinky a tiskoviny
Power Cable
Circuit Integrity 90 Minutes acc. to DIN 4102-12
Insulation Integrity FE180 acc. to DIN VDE 0472-814
halogenfree with improved behaviour in case of fire acc. to DIN VDE 0266
Application
ALSECURE RHEYHALON Security cables N2XH-O/J with 90 minutes circuit integrity should be used for DIN installations for security equipments in public buildings, e.g. meeting areas, schools etc. (DIN VDE 0108) as well as in hospitals (DIN VDE 0107) or other safety relevants areas where a circuit integrity acc. to DIN 4102-12 over 90 minutes for power distribution is required.
This cable is suitable for interior installations on, in and under plaster, in dry, wet and damp rooms as well as in masonry and in concrete. A direct installation in ground and water is not allowed. An installation in open air areas requires a protection from sun light (UV-radiation). Under usage of tubes an outdoor or ground installation is possible, if the cable is guarded against water and moisture.
This cable conforms to the circuit integrity requirements of E90 in accordance with DIN 4102-12 and of the requiremants of the 'Brandschutztechnischen Richtlinien' (supplement 1 to DIN VDE 0108). The circuit integrity is guaranteed by an operating voltage of 400 V.
Standards
circuit integrity E90 DIN VDE 4102-12
insulation integrity FE180 IEC 60331 and VDE 0472-814
halogen free IEC 60754-2 and EN 50267-2-1
corrosive gases IEC 60754-2 and EN 50267-2-2
flame retardant IEC 60332-3 and EN 50266-2-4 und -2-5
smoke density IEC 61034-2 and EN 50268-2
fire retardant IEC 60332-1-2 and VDE 0482-265-2-1
*depending on the method of installation regarding to ABP (general construction inspection test certificate)