Application
RHEYHALON Security cables N2XCH with 90 minutes circuit integrity should be used for DIN installations for security equipments in public buildings, e.g. meeting areas, schools etc. (DIN VDE 0108) as well as in hospitals (DIN VDE 0107) or other safety relevants areas where a circuit integrity acc. to DIN 4102-12 over 30 - 60* minutes for power distribution is required.
This cable is suitable for interior installations on, in and under plaster, in dry, wet and damp rooms as well as in masonry and in concrete. A direct installation in ground and water is not allowed. An installation in open air areas requires a protection from sun light (UV-radiation). Under usage of tubes an outdoor or ground installation is possible, if the cable is guarded against water and moisture.
This cable conforms to the circuit integrity requirements of E 90 in accordance with DIN 4102-12 and of the requiremants of the Brandschutztechnischen Richtlinien (supplement 1 to DIN VDE 0108). The circuit integrity is guaranteed by an operating voltage of 400 V.
Design
- Conductor
Bare copper; solid class 1, stranded class 2
acc. to DIN VDE 0295
- Conductor taping
MICA tape
- Core insulation
cross linked polyethylene compound 2XJ1
acc. to DIN VDE 0276-604
- Inner covering
halogen free filling compound
- Concentric conductor
Bare copper wires with counter helix
- Outer sheath
thermoplastic, halogen free polyolefin compound HM4
acc. to DIN VDE 0276-604
- Sheath colour
orange
Standards
circuit integrity E90 DIN VDE 4102-12
insulation integrity FE180 IEC 60 331 und VDE 0472-814
halogen free IEC 60 754-2 und EN 50 267-2-1
corrosive gases IEC 60 754-2 und EN 50 267-2-2
flame retardant IEC 60 332-3 und EN 50 266-2-4 und -2-5
smoke density IEC 61 034-2 und EN 50 268-2
fire retardant IEC 60 332-1-2 und VDE 0482-265-2-1
|