2XS(FL)2Y RMS 64/110 (123)kV (Milliken)

Záložka Tisknout Kontaktovat nás
2XS(FL)2Y RMS 64/110 (123)kV (Milliken) Medzinárodní značení  64/110 (123)kV Copper segmented XLPE Cable, Cu-Screen, Al-laminated PE sheath
Single core segmented XLPE insulated cable, screen area longitudinally and radially watertight
Standart
Mezinárodní  IEC 60840
Popis

Stranded segmented copper conductor class 2 according to IEC 60228, semi conducting conductor screen, insulation of cross-linked polyethylene (XLPE), semi conducting insulation screen, semi conducting swellable bedding, copper screen, swellable bedding, aluminium tape bonded to PE sheath.

Application in ground, outdoors, in tubes, in water, indoors and in cable ducts.

Optionally aluminium and/or watertight conductor, semiconductive layer on PE sheath, embossed marking or Fiber Optics in screen area for temperature measurement available.

All high voltage cables are manufactured on the basis of specifications and can be adapted to the requirements of the customer. Therefore, all technical information are purely for information purposes and the electrical characteristics are calculated for values which are specified in the data sheets. For your specific requirements and laying arrangements please don't hesitate to contact us.


 Nahoře
Vlastnosti
Konstrukční charakteristika
Material jádra Copper  
Insulating material XLPE  
Screen Copper wire  
Outer sheath HDPE  
Bezolovnatý Yes  
Bezhalogenové Yes  
Rozměrová charakteristika
Nominal insulation thickness 15,0mm  
Electrical characteristics
Frequence 50Hz  
Operating voltage 110kV  
Thermal soil resistivity wet zone 1K*m/W  
Charakteristika použití
Minimum installation temperature -20°C  
Bending factor when installed 15(xD)  
Bending factor when laying 30(xD)  
Longitudinal water tightness Yes  
Max. conductor temperature in service 90°C  

 Nahoře
Váš výběr
Conductor cross-section  mm²
Number of systems  
Maximum operating voltage  kV
Laying depth, center of system  mm
Screen section  mm²
Ambient ground temperature  °C
Nominal outer sheath thickness  mm
Outer Diameter  mm
Approximate weight  kg/m
Maximum pulling force by laying  kN
Grounding type  
Load factor  
Thermal soil resistivity dry zone  K*m/W
Permissible current rating when buried  A
Permissible transmission capacity, buried  MVA
Použít
Obnovit
Výsledky   2/2
Výběr všech položek Nexans reference Conductor cross-section (mm²) Number of systems Maximum operating voltage (kV) Laying depth, center of system (mm) Screen section (mm²) Ambient ground temperature (°C) Nominal outer sheath thickness (mm) Outer Diameter (mm) Approximate weight (kg/m) Maximum pulling force by laying (kN) Grounding type Load factor
Produkt na objednávku V110120050 1200 1 123 1200 50 20 4,0 91 16,5 60 Solid bonding 0,7
Produkt na objednávku V110160050 1600 1 123 1200 50 20 4,0 97 21,5 80 Solid bonding 0,7
Přidat do favoritů

 Nahoře
Prodejní a dodací podmínky
The current and transmission capacity is calculated with the laying arrangement stated in the data sheet. The picture may show options.