ADP Specification

Removed
Záložka Kontaktovat nás
ADP Specification Secondary circuit cable 450/750 (1000V)
Standart
Národní standart  ADP
Popis

Applications

Connection between transformers and Airfield Lighting Equipments. This cable can be buried providing there is an extra mechanical protection.

Design

  1. Conductor: Stranded bare copper Class 2 Cross sectional area: 4 mm2
  2. Insulation: XLPE (cross linked polyethylene) Colour: Black

 Nahoře
Vlastnosti
Konstrukční charakteristika
Material jádra Bare copper  
Conductor flexibility Stranded class 2  
Isolace XLPE (chemical)  
Sheath colour Black  
Rozměrová charakteristika
Conductor cross-section 4mm²  
Minimum outer diameter 3,5mm  
Maximum outer diameter 4,5mm  
Počet jader 1  
Approximate weight 42kg/km  
Electrical characteristics
Voltage drop, single phase 9,56V/A.km  
Rated Voltage Uo/U (Um) 450 / 750 V  
Permissible current (one phase) 42,0A  
Maximum operating voltage 1000V  
Mechanical characteristics
Mechanical resistance to impacts Good  
Cable flexibility Rigid  
Charakteristika použití
Max. conductor temperature in service 90°C  
Field of application Secondary Circuit  
Weather resistance Good  
Chemická odolnost Very good  
Water proof Temporary  
Ambient installation temperature, range -20 .. 70°C  
Packaging Cut to length  

 Nahoře
Výsledky   1/1
Výběr všech položek Nexans reference Jméno
24.1   Removed ADP 1x4
Přidat do favoritů

 Nahoře
Prodejní a dodací podmínky

Marking

SECONDARY CIRCUIT 1 x 4 mm2 450/750 - 205 month - year