About Nexans
Produkty a řešení
Služby zákazníkům
Pracovat pro Nexans
Novinky a tiskoviny
Flexible interconnection cable for 400Hz power supply systems. Suitable for use outdoor when freely moved or for cable car operation and as reeling cable.
Rated voltage
A.C. test voltage
power core/power core/control cores
3.5 Kv/5 min
control core/control core
2 Kv/5 min
D.C. conductor resistance at 20°C
core 25 mm²
≤ 0.780 Ω/km
core 35 mm²
≤ 0.554 Ω/km
core 1 mm²
≤ 19.5 Ω/km
2 cores 25 mm² located opposite in parallel
≤ 0.390 Ω/km
3 cores 35 mm² located opposite in parallel
≤ 0.277 Ω/km
Inductance and inductive resistance at 400Hz, two opposite cores in parallel connected
Planning reference value calculated from measured values
25 MM²
L = 0.13 mH/km
X = 0.325 Ω/km
35 MM²
L = 0.1 mH/km
X = 0.25 Ω/km
Temperatures
Limit temperature at conductor
during operation
+ 90°C
during short circuit
+ 200°C
during short circuit for soft solder connections
+ 160°C